Steam drum level control studies of a natural circulation multi loop reactor

2013 
Abstract The proposed heavy water moderated and light water cooled pressure tube type boiling water reactor works on natural circulation at all power levels. It has parallel inter-connected loops with 452 boiling channels in the main heat transport system configuration. These multiple (four) interconnected loops influence the steam drum level control adversely through the common reactor inlet header. Alternate design studies made earlier for efficient control of SD levels have shown favorable results. This has lead to explore further the present scheme with the compartmentalization of CRIH into four compartments catering to four loops separately. The conventional 3-element level control has been found to be working satisfactorily. The interconnections between ECCS header and inlet header compartments have also increased the safety margin for various LOCA and design basis events. The paper deals with the SD level control aspects for this novel MHT configuration which has been analyzed for various PIEs (Pos...