Predominant bacterial genera in granular activated carbon water treatment systems

1986 
Granular activated carbon (GAC) beds may be used for removal of dissolved organic matter during the treatment of drinking water. However, they might also change the microbiological quality of the water entering the distribution system either by changing the predominant bacteria or the bacterial density of the treated water. A 3-year pilot plant study of water treatment using GAC beds was conducted at the Baxter Water Treatment Plant in Philadelphia. During the study, bacteria were isolated from the raw water and from the effluents of the GAC treatment units. At the end of the study, bacteria were also isolated from the GAC units and from sand beds operated in parallel with the GAC units. Bacterial genera in the GAC effluents and in the GAC units themselves were similar to those found in the raw water and in the sand beds. Prechlorination and (or) preozonation of the water before GAC treatment had no noticeable effect on the bacterial genera found as compared with GAC unit having no predisinfection. The ba...