Analysis on combinations of indoor thermal microclimate parameters in radiant cooled residential buildings and drawing of new thermal comfort charts

2016 
This paper proposed to discuss some issues about indoor microclimate parameters design in radiant cooled residential buildings. Based on the thermal comfort model, the relationships between low mean radiant temperature and other thermal microclimate parameters such as indoor air temperature, air velocity, and relative humidity were analyzed. The improved and reasonable combinations of four thermal microclimate parameters including radiant cooling surface temperature, air temperature, air velocity, and relative humidity were further derived. Furthermore, a number of new thermal comfort charts using radiant cooling surface temperature and air temperature as dominant parameters were drawn. The results show that the air temperature can be increased 1–3℃ within the recommended thermal comfort range when the mean radiant temperature is reduced 3℃. Under the design goal of thermal neutral, when the chilled ceiling surface temperature is in the range of 16–26℃, the air temperature should be set at 25.3–29.3℃; whe...