Indoor air quality investigation of a badminton hall in humid season through objective and subjective approaches

2021 
Abstract This study investigated the indoor air quality (IAQ) during humid season in an old badminton hall, to explore the IAQ characteristics of natural ventilated sports buildings for public use. The indoor air parameters (temperature, relative humidity and air velocity) and indoor air pollutants (CO2, TVOC, PM2.5 and PM10) were measured. A subjective approach was carried out through questionnaire survey. 185 valid questionnaires were recovered, and 68.7% of the participants had exercised. Results show that the indoor air qualities obtained through objective and subjective approaches were obviously different. Indoor PM, TVOC and CO2 concentrations were normal, but 37.3% of the participants complained about the building materials' smell and 73.5% of the participants reported obvious sweaty odor. Physical activity might reduce a person's sensitivity to the environment. The participants generally felt warm and hot because of the high relative humidity. Post-exercise participants felt significantly hotter than those who did not exercise, and were generally more receptive to IAQ. The method of Fanger was employed to narrow the gap between subjective and objective approaches with a modified parameter, and to furtherly estimate the ventilation. The present study demonstrates the necessity to combine two approaches together to assess the IAQ in sports buildings.
    • Correction
    • Source
    • Cite
    • Save
    • Machine Reading By IdeaReader
    65
    References
    1
    Citations
    NaN
    KQI
    []