Some measurement techniques of distribution line impedance on hot-line

2005 
The line impedance could be measured by means of only passive elements such as inductors or resistors, that is presented at first. However, as the voltage and current used for the measurement are increased, the size of the inductor or resistor being used also needs to be increased, so in practice it would be virtually impossible to make an accurate measurement. Because of this, we have developed a novel measurement method for line impedance using an inverter circuit, which we describe secondly. In the third place, we propose another line impedance measurement method. The novel method is that the high frequency wave with minimum voltage is injected into the distribution line system. By means of this method, the line capacitance and the line inductance can be measured. These proposals are confirmed by the simulation or experiment
    • Correction
    • Source
    • Cite
    • Save
    • Machine Reading By IdeaReader
    4
    References
    2
    Citations
    NaN