Development and Validation of a Special Protection System for Internal Fault in a High-Power Three-Level NPC VSC

2021 
This paper describes the development and validation of an innovative protection system based on medium-voltage fuses for a high-power switching conversion system. This special conversion system, rated to deliver about 56 MW to the load, is based on neutral-point clamped IGCT inverters, connected to the same dc link through a set of distributed busbars, with a dc-link voltage of 6.5 kV and a capacitive stored energy up to 837 kJ. The sudden release of this energy in case of a switch failure in one inverter and the subsequent short circuit of one leg can lead to destructive consequences. From the analysis of different protection strategies, performed by numerical simulations of the fault evolutions, the developed solution based on medium-voltage fuses was found the only provision able to cope with such high stored energy and uncommon circuit topology. Custom fuses were developed for this application, and a specially tailored test was designed for validating the fuse selection. The paper, after summarizing the work carried out to simulate the fault evolution and select the protection, presents the analyses carried out to set up the validation test, and describes and discusses the results of the test and the complementing numerical simulations, which demonstrated the effectiveness of the protection system.