A Relationship Between Minimum Arcing Interrupting Capability and Opening Velocity of Vacuum Interrupters in Short-Circuit Current Interruption

2018 
Controlled switching technology operates circuit breakers at the minimum arcing time for short-circuit current interruption. However, there is no report to reveal a relationship between the short-circuit current interrupting capability with the minimum arcing time and the opening velocities of vacuum interrupters. The objective of this paper is to reveal a relationship between the short-circuit current interrupting capability with the minimum arcing time and the opening velocities of vacuum interrupters. A 40.5-kV fast vacuum circuit breaker prototype was built up which was equipped with a commercial 40.5 kV–31.5 kA vacuum interrupter and it was driven by an electromagnetic repulsion mechanism. It provided an average velocities ranging from 2.5 to 5.5 m/s. A total of 50 times of 40-kA short-circuit current interrupting tests were carried out in a synthetic circuit. Test results showed that the minimum arcing time of successful interruption decreased with the increasing of the average opening velocity. The minimum arcing gap was determined as 1.8 mm and it kept as a constant as the average opening velocity increased. The experimental results also showed a relationship between the arc energy density and the arc extinguishing gap, which acted a linear boundary between the successful and failure short-current interruptions.