Dynamic Modeling and Operation Characteristics Analysis of LiBr Absorption Heat Pump

2021 
In order to fully exploit the dynamic operation characteristics of absorption heat pump, a dynamic simulation model of LiBr absorption heat pump considering mass transfer and distribution parameters is established. The thermal inertia characteristics of the system are studied, and the thermal performance and crystallization characteristics of the system are analyzed under the conditions of heat source temperature change, cooling water temperature change and refrigerant water temperature change. The results show that: the model can accurately simulate the steady-state and dynamic characteristics of the absorption heat pump; the thermal inertia of the unit is mainly related to the mass of the solution stored in the unit; the upper limit of the heat source inlet temperature is affected by the COP of the system and the crystallization risk, the decrease of the inlet temperature of cooling water can increase the COP of the system, and the lower limit is limited by the crystallization risk, and the cooling water inlet temperature is affected by the crystallization risk , and the lower limit of the inlet temperature of cooling water is limited by the crystallization characteristics. The upper limit of the inlet temperature of refrigerant water is not limited by the crystallization characteristics, but is mainly limited by the user’s energy demand. This provides a reference for the dynamic operation of absorption heat pump.
    • Correction
    • Source
    • Cite
    • Save
    • Machine Reading By IdeaReader
    7
    References
    0
    Citations
    NaN
    KQI
    []