Root cause evaluation of pressurizer relief valve leakage

1996 
Pressurizer relief valves at two pressurized water reactor units experienced unacceptable leakage during plant heatup. The leakage was suspected to be caused by excessive pipe loads on the valves. This paper describes how monitoring via hard-wired transducers and a digital data acquisition system was used to quantify the pipe loads on the valves, and assist in determining the root cause of the pipe loads and appropriate corrective actions. The selection of the parameters monitored, how the monitoring was accomplished and interpretation of the results is discussed. The corrective actions implemented based on the monitoring results are also discussed.