Evaluation of performance an air conditioning systems using t-junction flash gas refrigerant

2018 
The purpose of this study was to determine the performance of air-cooled chiller system using T-junction flash gas bypass refrigerant. The experiment was conducted by installing T-junction after expansion device to separate the phase of refrigerant liquid and gas which flows to the evaporator. The working fluid is used as a cooling medium is R-290. To get performance data, measurements performed at the time of steady state when the water chilling temperature T = 15 C up to T = 10 C and flow rates kept constant at 1 GPM (6.3 x 10-5 m3/s). Finally, the use of T-junction mode in AC system generates an increase in the refrigerating effect and coefficient of performance systems (CoP) by 6% and 17.8 %, respectively. Also, it can decrease the heat of compression by 8.5%. This has implications for the lighter compressor work and saving the power consumption of the AC system.