First-zone distance relaying algorithm of parallel transmission lines for single-phase to ground faults

2016 
Abstract A novel zone-one distance relaying algorithm for single phase to ground faults on parallel lines is proposed. The proposed algorithm only requires sampled current and voltage values at one end of the protected line to calculate the fault impedance. The adjacent circuit zero-sequence current can be calculated from the protected circuit zero-sequence current and without cross-connection. The algorithm can overcome the issues of overreach and under-reach. The study in this paper shows that the new algorithm has higher reliability than that of conventional distance relays with and without cross-connected zero-sequence current compensation. Therefore, the algorithm optimizes the performance of zone-one distance relaying for parallel transmission lines. The results are verified by the simulations using PSCAD software.