Room air stratification in combined chilled ceiling and displacement ventilation systems

2011 
Radiant chilled ceilings with displacement ventilation (DV) represent a promising integrated system design that combines the energy efficiency of both sub-systems with the opportunity for improved ventilation performance resulting from the thermally stratified environment of DV systems. The purpose of this study was to conduct laboratory experiments for a typical U.S. interior zone office to investigate how room air stratification is affected by the ratio of cooling load removed by a chilled ceiling to the total cooling load, η, for two different chilled ceiling configurations. The experiments were carried out in a climatic chamber equipped with radiant panels installed in the suspended ceiling. In the first test configuration representative of thermally activated slab applications, 12 panels covering 73.5% of the ceiling were used. During the second series of tests, 6 panels covering 36.7% of the ceiling were used, representing a typical installation of metal radiant panels. The cooling load removed by t...
    • Correction
    • Source
    • Cite
    • Save
    • Machine Reading By IdeaReader
    15
    References
    29
    Citations
    NaN
    KQI
    []