Experimental study of the combined effect of the refrigerant charge, compressor speed and expansion valve opening in a refrigeration system.

2007 
An experimental study has been performed to evaluate the effect of refrigerant charge, electronic expansion valve opening and compressor speed on the thermodynamic performance of a vapour compression refrigeration system. A testing apparatus comprised of a variable speed compressor, a pulse width modulated electronic expansion valve and a device for varying the refrigerant charge, was designed and constructed. It has been found that for a given refrigerant charge the COP at a particular compressor speed can be maximized by a proper opening of the expansion valve. It has also been shown that the optimum evaporator superheat is within a range of 1 to 3°C.
    • Correction
    • Source
    • Cite
    • Save
    • Machine Reading By IdeaReader
    0
    References
    6
    Citations
    NaN
    KQI
    []