Age-related degradation of Westinghouse 480-volt circuit breakers

1990 
After the McGuire event in 1987 relating to failure of the center pole weld in one of its reactor trip breakers, activities were initiated by the NRC to investigate the probable causes. A review of operating experience suggested that the burning of coils, jamming of the operating mechanism, and deterioration of the contacts dominated the breakers failures. Although failures of the pole shaft weld were not included as one of the generic problems, the NRC augmented inspection team had suspected that these welds were substandard which led them to crack prematurely. A DS-416 low voltage air circuit breaker manufactured by Westinghouse was mechanically cycled to identify age-related degradations. This accelerated aging test was conducted for over 36,000 cycles during nine months. Three separate pole shafts, one with a 60 degree weld, one with a 120 degree and one with a 180 degree were used to characterize the cracking in the pole level welds. In addition, three different operating mechanisms and several other parts were replaced as they became inoperable. The testing yielded many useful results. The burning of the closing coils was found to be the effect of binding in the linkages that are connected to this device. Among themore » seven welds on the pole shaft, {number sign}1 and {number sign}3 were the critical ones which cracked first to cause misalignment of the pole levers, which, in turn, had led to many problems with the operating mechanism including the burning of coils, excessive wear in certain parts, and overstressed linkages. Based on these findings, a maintenance program is suggested to alleviate the age-related degradations that occur due to mechanical cycling of this type of breaker. 3 refs., 39 figs., 7 tabs.« less
    • Correction
    • Source
    • Cite
    • Save
    • Machine Reading By IdeaReader
    0
    References
    1
    Citations
    NaN
    KQI
    []