Modeling, calibration, and sensitivity analysis of a direct expansion AHU-Water source VRF system

2020 
Abstract The term variable refrigerant flow (VRF) refers to the ability of a system to control the amount of refrigerant flowing to multiple evaporators (indoor units), which enables the use of many evaporators of differing capacities and configurations connected to a single condensing unit. The arrangement provides individualized comfort control and simultaneous heating and cooling in different zones. In this study, a performance prediction model of a DX AHU (direct expansion air handling unit)-water-source VRF heat pump system was constructed based on EnergyPlus, MATLAB and BCVTB using actual measured data. Advanced control logic using an EMS function was used in EnergyPlus for outdoor unit modeling, while prediction models for a cooling tower, boiler and pump were constructed in Matlab. In order to predict the model's quantitative energy consumption, performance curves and power consumption were calculated. The calculations were checked by comparing them with actual data and the performance curves were then calibrated. The validity test results after the calibrations showed reliable results with a Cv(RMSE) error rate of 14.5%. Based on these results, we performed a sensitivity analysis of the DX AHU-water-source VRF system's cooling energy according to the AHU discharge air temperature, refrigerant evaporative temperature and entering condenser fluid temperature and flow rate.