Automatic control of external carbon source addition for nitrogen removal in sewage with low C/N ratios

2004 
For cost-effective nitrogen removal from sewage with low C/N ratios, an automatic control system for the addition of external carbon based on oxidation-reduction potential (ORP) data in an anoxic reactor has been developed. In this study, it was carried out with a pilot-scale modified Bardenpho process. This consisted of anoxic1, aerobic1, anoxic2 and aerobic2 stages with an external recycle ratio of 150% (Q/Qinf), and a media packing ratio of 2.4%-2.9% (v/v) in the aerobic reactor. As a result of applying the automatic control system for the minimization of the external carbon source dosage, the dosage was decreased by about 20%. This estimate was based on ORP compared with a stable dosage of 75mg/L based on the C/NOx-N ratio of the anoxic influent. It was necessary that the ORP set-value be regulated from -120 mV to Ð80 mV because influent NH4+-N concentration varied from 12 to 15 mg/L due to rainfall. Correspondingly, the demanded dosages were decreased. Drift of the the real-time value in control system was more stable after changing the ORP set-value from -120 mV to -80 mV.